- Heavy Duty skid designed for lifting or towing in either direction
- New ABB 5/15kV Non fusible Load Break Switch with door interlock and Aux switch to open Toshiba breaker if door is open
- New Toshiba HV6AS-L 7.2kV 630a Manually operated Vacuum breaker
- SMC D-4000 HV Monitor
- SEL 751a Feeder protection relay
- 2ea 35:1 PTs for metering
- New 500kVA N3R Dry type transformer 480D-4160Y (step-up design)
- New 2400V L-N Neutral Grounding resistor
- New Startco SE-325 NGR Monitor with ER-5kV Sensing resistor
- N3R/12 Enclosure with door behind door construction